Fluke 435 Series II Basic Power Quality and Energy Analyzer Fluke 435 Series II Basic Power Quality and Energy Analyzer Advanced power quality functions and energy monetization capabilities mean there is no electrical issue the Fluke 435 Series II can’t handle P000258 Power Quality Analyzers 0 VND Quantity: 1 Cái


  •  
  • Fluke 435 Series II Basic Power Quality and Energy Analyzer

  • Post on 23-09-2015 10:12:08 AM - 1214 Views
  • Price: Contact

  • Advanced power quality functions and energy monetization capabilities mean there is no electrical issue the Fluke 435 Series II can’t handle


Quantity

Advanced Power Quality Functions, Unprecedented Energy Analysis Capabilities

Power quality issues can affect the operation of critical loads and have a negative impact on your bottom line. Think of the Fluke 435 II Power Quality and Energy Analyzer as your insurance policy. The Fluke 435 Series II Power Quality and Energy Analyzer is the world's only Power Quality analyzer that can monetize the cost of energy waste due to poor power quality. The wide range of measurement functions and measurement methods in the Fluke 435-II make it the ideal tool for both power quality troubleshooting and discovering energy savings Whether you’re checking the performance of motors and generators, trying to discover the source of an intermittent power problem or performing an energy study the Fluke 435-II will give you the data you need to quickly get to the heart of the problem.

Wrapped in a lightweight, rugged package, the Fluke 435 II Energy Analyzer is the ideal portable power quality instrument providing advanced power quality functionality and energy analysis capabilities. If you require the same advanced functionality at a higher frequency, Fluke 437 II is the must-have power quality analyzer for 400 Hz power systems.

Applications

  • Frontline Troubleshooting – Quickly diagnose problems on-screen to get your operation back online.
  • Long-Term Analysis – Uncover hard-to-find or intermittent issues.
  • Load Studies – Verify the available electrical system capacity before adding loads
  • PowerWave Data Capture – Capture every waveform for up to 5 minutes along with fast RMS values so you can determine how the voltage, current and frequency values are interacting.
  • Power Inverter Efficiency – Measure the input and output power simultaneously to discover whether the inverter is optimized for its application.
  • Energy Monetization – Calculate the fiscal cost of energy waste due to poor power quality.
  • Energy Assessment –Quantify the before and after installation improvements in energy consumption to justify energy saving devices.
  • Predictive Maintenance – Periodic benchmarking of the power system can help detect and prevent power quality issues before they cause downtime.
Product Specifications
Volt Model Measurement Range Resolution Accuracy
Vrms (ac+dc) 1 V to 1000 V phase to neutral 0.01 V ± 0.1% of nominal voltage**** 
Vpk 1 Vpk to 1400 Vpk 1 V 5% of nominal voltage
Voltage Crest Factor (CF) 1.0 > 2.8 0.01 ± 5%
Vrms½   0.1 V ± 0.2% of nominal voltage
Vfund   0.1 V ± 0.1% of nominal voltage
Amps (accuracy excluding clamp accuracy)
Amps (ac+dc) i430-Flex 1x  5 A to 6000 A 1 A ± 0.5% ± 5 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ± 0.5% ± 5 counts
1mV/A 1x 5 A to 2000 A 1A ± 0.5% ± 5 counts
1mV/A 10x 0.5 A A to 200 A (ac only) 0.1 A ± 0.5% ± 5 counts
Apk i430-Flex  8400 Apk  1 Arms ± 5%
1mV/A 5500 Apk 1 Arms ± 5%
A Crest Factor (CF) 1 to 10 0.01 ± 5%
Amps½ i430-Flex 1x  5 A to 6000 A  1 A  ± 1% ± 10 counts 
i430-Flex 10x 0.5 A to 600 A 0.1 A  ± 1% ± 10 counts
1mV/A 1x   5 A to 2000 A  1A  ± 1% ± 10 counts
1mV/A 10x 0.5 A A to 200 A (ac only) 0.1 A ± 1% ± 10 counts
Afund i430-Flex 1x  5 A to 6000 A 1 A ± 0.5% ± 5 counts 
i430-Flex 10x  0.5 A to 600 A 0.1 A ± 0.5% ± 5 counts
1mV/A 1x  5 A to 2000 A 1A ± 0.5% ± 5 counts
1mV/A 10x  0.5 A A to 200 A (ac only) 0.1 A ± 0.5% ± 5 counts
Hz
Fluke 434 @ 50 Hz Nominal 42.50 Hz to 57.50 Hz 0.01 Hz  ± 0.01 Hz
Fluke 434 @ 60 Hz Nominal 51.00 Hz to 69.00 Hz 0.01 Hz ± 0.01 Hz
Power
Watts (VA, var) i430-Flex  max 6000 MW 0.1 W to 1 MW ± 1% ± 10 counts
1 mV/A max 2000 MW 0.1 W to 1 MW ± 1% ± 10 counts
Power Factor (Cos j/DPF) 0 to 1 0.001 ± 0.1% @ nominal load conditions
Energy
kWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and V nominal ± 1% ± 10 counts
Energy Loss i430-Flex 10x Depends on clamp scaling and V nominal ± 1% ± 10 counts Excluding line resistance accuracy
Harmonics
Harmonic Order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-Harmonic Order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts % f 0.0% to 100% 0.1% ± 0.1% ± n x 0.1%
r 0.0% to 100% 0.1% ± 0.1% ± n x 0.4%
Absolute 0.0 to 1000 V 0.1 V ± 5% *
THD 0.0% to 100% 0.1% ± 2.5%
Amps % f 0.0% to 100% 0.1% ± 0.1% ± n x 0.1%
r 0.0% to 100% 0.1% ± 0.1% ± n x 0.4%
Absolute 0.0 to 600 A 0.1 A ± 5% ± 5 counts
THD 0.0% to 100% 0.1% ± 2.5%
Watts % f or r  0.0% to 100% 0.1% ± n x 2%
Absolute Depends on clamp scaling and V nominal  ± 5% ± n x 2% ± 10 counts
THD 0.0% to 100%   0.1% ± 5%
Phase Angle -360° to +0° ± n x 1°
Flicker
Plt, Pst, Pst(1min) Pinst 0.00 to 20.00 0.01 ± 5%
Unbalance
Volts % 0.0% to 20.0% 0.1% ± 0.1%
Amps % 0.0% to 20.0% 0.1% ± 1%
Mains Signaling
Threshold Levels Threshold, limits and signaling duration is programable for two signaling frequencies
Signaling Frequency 60 Hz to 3000 Hz 0.1 Hz  
Relative V% 0% to 100% 0.10% ± 0.4%
Absolute V3s (3 second avg.) 0.0 V to 1000 V 0.1 V ± 5% of nominal voltage
General Specifications
Case Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
Display Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
Memory 8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size)
Real-Time Clock Time and date stamp for Trend mode, Transient display, System Monitor and event capture
Environmental
Operating Temperature 0°C ~ +40°C; +40°C ~ +50°C excl. battery
Storage Ttemperature -20°C ~ +60°C
Humidity +10°C ~ +30°C: 95% RH non-condensing 
+30°C ~ +40°C: 75% RH non-condensing 
+40°C ~ +50°C: 45% RH non-condensing
Maximum Operating Altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V 
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V 
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility (EMC) EN 61326 (2005-12) for emission and immunity
Interfaces Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
Warranty Three years (parts and labor) on main instrument, one year on accessories
 
*  ± 5% if ≥ 1% of nominal voltage ± 0.05% of nominal voltage if < 1% of nominal voltage
**  50Hz/60Hz nominal frequency according to IEC 61000-4-30
***  400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode
**** For nominal voltage 50 V to 500 V
     

 